4.6 BATTERY 
MAINTENANCE
The battery should be inspected per the "Service 
Schedule" section. The following procedure should be 
followed for inspection:
1.  Inspect the battery posts and cables for tightness 
and corrosion. Tighten and clean as necessary.
2.  Check the battery fluid level of unsealed batteries 
and, if necessary, fill with Distilled Water Only. Do 
not use tap water in batteries.
3.  Have the state of charge and condition checked. 
This should be done with an automotive-type bat-
tery hydrometer. 
DANGER
  Do not dispose of the battery in a fire. The 
battery is capable of exploding.
  A battery presents a risk of electrical shock 
and high short circuit current. The following pre-
cautions are to be observed when working on 
batteries:
•  Remove the 15A fuse from the generator control 
panel.
• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
•  Do not lay tools or metal parts on top of the 
battery; and
•  Disconnect charging source prior to connecting or 
disconnecting battery terminals.