Quantum ATL P7000 Unpacking Instructions
Document 6434006-02, Ver. 2, Rel. 0
August 2002
Selecting an Installation Location
5
Floor Strength and 
Inclination
0
The floor at the installation site must be rated at 250 lb/ft
2
 
(1221 kg/m
2
). This is sufficient to support a fully loaded ATL P7000 
library. 
The floor must be level to within 0.25 inch (6.4 mm) over a 6-foot-by-6-
foot (1.83-meter-by-1.83-meter) area.
Power and 
Grounding
0
For the United States and Canada, one or two UL/CSA certified power 
cords are furnished. Each uses a 14/3 SJT cord, a 5-20P plug, and an 
IEC-C320 C19 female connector (see 
).
Figure 3  Power Supply 
Cord
The library is rated 100-240V~, 50-60Hz, 16A-8A, 1600W. 
The library power requirements may require modification of the 
facilities existing power capabilities by a qualified electrician. The 
required wall outlet for the United States and Canada is rated at 125V 
20A (see 
).
Figure 4  Wall Outlet
The dedicated wall outlet and a 20 amp circuit breaker must provide 
power to the ATL P7000 only. Outside North America, replace the 
supplied power cord with a harmonized 3 x 1.5 mm
2
 power cord that 
is approved by the country where used, and install the appropriate 
wall outlet. More information on the electrical requirements is 
provided in the ATL P7000 Pre-Installation Site Survey Instructions.
Caution:
The ATL P7000 must be connected to a grounded 
electrical outlet.
Plug:
NEMA 5-20
Connector:
IEC-C320 C19
Connects to
wall outlet
Connect to library
power supply
Neutral
Ground
Line
Wall outlet:
NEMA 5-20R
rated 125V 20A