Operating the Web Control Panel
Cybernetics
UM-MV-86-B1-0801
To test the configuration, pull the AC power plug on the UPS. The “Messages” tab on the
Web Control Panel should give a message that the UPS is on battery power. Wait a few
seconds, then plug the UPS AC power back in. The “Messages” tab on the Web Control
Panel should give a message that power has been restored.
Configuring a Tripp Lite® SmartPro®/SmartOnline™ model UPS with 
SNMPWEBCARD
You must configure the SNMPWEBCARD’s network parameters so the SmartPro®/
SmartOnline™ can communicate with the HSTC. Under “Settings” > “Contacts” >
“SNMP” > “New”, enter the following information:
IP Address
[IP address of HSTC]
Name
[A descriptive name (e.g., miSAN-V-Series)]
Community
public
Trap Port
162
Under “Settings” > “Events”, check “SNMP Notification” for “On Battery”, “Battery Low”,
and “Battery Capacity Below Warning Level”. When you check “SNMP Notification”, a
window will pop up with more configuration options. Under “Message Settings”, set the
two time values to 
0. Under “IP Addresses”, highlight the HSTC’s IP address so the HSTC
is notified of the event. Also, make sure the “Shutdown” action for the “On Battery” event
is not checked, since this could cause a loss of output power without an SNMP warning
message.
Under “Settings” > “Device” > “Low Battery Warning”, enter the percentage of the battery
charge that you want to trigger the HSTC shutdown. Note that a loss of output power can
occur before 0% is reached, so do not use a value that is too low. Cybernetics recom-
mends a minimum value of 30 or more, depending on the load.
 
Note 
   
From the miSAN-V-Series’s Web Control Panel, make sure “Receive 
SNMP messages from UPS” is set to Enabled. 
 
Note 
   
The APC Smart-UPS model does not send SNMP power failure 
messages when using the diagnostics function for simulating a power 
failure, so you cannot use this diagnostic to test the communication 
with the miSAN-V-Series.