Chapter 7. Robotic Assembly Replacement
22
Halting Backups
Backups are interrupted if the robotic assembly, sometimes referred to as a picker,
malfunctions, because tapes cannot be moved to or from drives. Also, backups cannot
run during the replacement of the robotic assembly, since the library must be powered
down.
malfunctions, because tapes cannot be moved to or from drives. Also, backups cannot
run during the replacement of the robotic assembly, since the library must be powered
down.
Use your backup software to stop any backups running to the library. You can restart
them once the robotic assembly has been replaced, the library has been powered on,
and diagnostics have been completed.
them once the robotic assembly has been replaced, the library has been powered on,
and diagnostics have been completed.
Preparing the Library
1.
Use the LC to verify that all drives are empty and do not contain media;
reference the Spectra T120 Library User Guide for instructions.
reference the Spectra T120 Library User Guide for instructions.
2.
Look through the library’s front to verify that the robotics are not moving; the
robotic assembly should be parked at the bottom of the library.
robotic assembly should be parked at the bottom of the library.
3.
From the LC’s toolbar menu, select Maintenance > Diagnostics. The Diagnostics
screen appears (Figure 7-1).
screen appears (Figure 7-1).
4.
Select Show Advanced; the Advanced Diagnostic Confirmation screen appears.
Figure 7-1 The Diagnostics screen.