Facility Requirements
Environmental Requirements
Air Quality
The Spectra T950 library contains an air filter that keeps the inside of the library 
free from particulates that might contaminate its components. Regular inspection 
and replacement of the air filter is necessary to keep the library functioning at 
optimal levels; Spectra Logic recommends that the filter be inspected at least once 
every three months and replaced as frequently as necessary.
Altitude
The library must operate between sea level and 10,000 feet (3,048 meters).
Fire Protection
It is presumed that customers’ data centers are outfitted with fire suppression 
equipment. Spectra Logic recommends that the Spectra T950 library be installed 
close to fire suppression equipment. To comply with the OSHA Directive for Fixed 
Extinguishing Systems (General, 1910.160), the Spectra T950 library has a punch-
out in the top of its frame for the purpose of attaching a hose or nozzle from your 
site’s fixed extinguishing system.
Power
The Spectra T950 library comes with dual AC power inputs. Each of these inputs 
should be connected to separate circuits, which allows for failover in the event of a 
power failure in one of the circuits. The table below shows the specifications for 
each of the power inputs.
TheT950 power receptacles are located in the lower right-hand corner as you face 
the back of the library.
Power Requirements
Electrical Rating
200-240 VAC, 15A, 50-60 Hz
Power Consumption
Nominal: 1,300 watts
Maximum: 3,600 watts
Heat Load
Nominal: 4,440 BTU/hour
Maximum: 12,295 BTU/hour
Power Cord 
a
a. Power cord approved for use in North America. See the 200-240-volt Ac Power Cables And Plugs table on page 13 for 
information on international power cords.
Three-conductor, 14-gauge, IEC320-C19, 16A, UL and CSA