Precautions
Installation Precautions
The Spectra T950 library will be installed for you by a certified Spectra Logic field 
engineer. Do not attempt to install the library yourself.
Library Placement Precautions
Data Center Flooring
The installed single-frame library can weigh up to approximately 2,156 pounds 
(978 kg) when fully loaded with the maximum number of tape drives and 
cartridges. Some data center floors may require reinforcement to hold this weight. 
Check your site’s flooring for load-bearing specifications. The library must be 
installed on hard flooring (for example, not on carpeting). Each additional frame 
may weigh up to 1,500 pounds (680 kg), depending on how the frame is 
configured. For details on the cascaded frames and related floor load requirements, 
refer to Cascade Load Distribution on page 20.
Note:
Spectra Logic is not responsible for damage caused to the library 
or its surroundings if the floor is not adequately reinforced. 
Electrical Cabling
All electrical cabling must meet the specifications outlined in Power on page 12. 
Failure to meet these specifications could damage your library, result in data loss, or 
both.
Note:
Adequate electrical cabling must be completed prior to the arrival 
of the field engineer on site for the library installation.