The LED bar graph functions as display for UPS 
utilisation.  The  signal  goes  off  during  this 
operations status every 2 seconds.
5.3.4
Unit Overload
The load on the UPS should never exceed the specified rated 
load  of  the  unit.  If  a  unit  overload  occurs  nevertheless  (from 
105%  ± 5%  of  the  specified  unit  rated  load)  the  fault  LED  is 
turned on accompanied with a signal tone (twice per second). 
The  connected  loads  continue  to  be  supplied  for  a  certain 
time  depending  on  the  level  of  the  overload.  However,  the 
connected load must be reduced without delay. 
Non-observance  of  the  "Unit  overload"  condition  may  cause 
the total loss of all UPS functions!
Also avoid short-term unit overloads, which may, for example, 
occur  when  connecting  a  laser  printer  or  laser  fax  machine. 
Do not connect any household appliances or machine tools to 
the UPS.
Never connect or switch on any additional loads 
to  the  UPS  if  there  is  a  mains  failure,  i.e.  if  the 
UPS is working in emergency power operation!
As a rule,  if there has never been an overload during normal 
operation,  there  will  not  be  one  during  battery  operation 
either.
The  signalling  of  the  fault  LED  in  combination 
with  a  continuous  alarm  points  out  a  switching 
of fault. Follow the instructions in chapter 6.