3  Commissioning 
Issue 03/01 
 
MICROMASTER 411 & COMBIMASTER 411    Operating Instructions  
48 
6SE6400-5CA00-0BP0  
 
Figure 3-4 
Control Circuit Jumpers 
Table 3-3 
Control Circuit Jumper Settings 
Jumper 
Jumper Fitted 
Jumper Removed 
Pot = Run 
P0700 = 2 
P0705 = 1 (motor potentiometer) 
P1210 = 6  automatic restart 
P0700 = 2 
P0701 = 1 
P1210 = 1 
24 AIN 
No software effect 
No software effect 
DC Brake 
Uses the jumper settings for the ramp settings by the 
duration of the direct current braking, to be calculated as 
follows. 
Duration of direct current braking = 
 
 
 
If the drive is quicker to  come to a standstill because of the 
load conditions, the direct current braking still remains 
active fo the calculated time time. 
Otherwise the value is held in P1233 (duration of the diret 
current braking) 
P1233 = 0 
Fan/Pump: M~n2 
P1300 = 2 (fan curve/quadratic vf) 
P1300 = 0 (linear vf) 
50/60 Hz 
Rated Motor Frequency = 60 Hz 
Rated Motor Frequency = 50 Hz 
Control Jumpers 
In Table 3-4 the behaviour of the Control Jumpers are explained. 
Table 3-4 
Control Circuit Jumper Behaviour 
Status before action(s)  Action(s) 
Reaction(s) of the inverter 
Jumper not fitted 
 
Power down 
 
Fit jumper(s) 
 
Power up 
Parameters influenced by jumper will have jumper default 
values 
Jumper fitted 
 
Cycle power 
Parameters influenced by jumper are not changed 
Jumper fitted 
 
Power down 
 
Remove jumper 
 
Power up 
Parameters influenced by jumper will have “jumper 
removed“ default values (normally factory default) 
Jumper not fitted 
 
Cycle power 
Parameters influenced by jumper are not changed 
 
P0305 (nominal motor current) 
r0207 (nominal inverter current) 
P1121 (deceleration time) *