3  Commissioning 
Issue 03/01 
 
MICROMASTER 411 & COMBIMASTER 411    Operating Instructions  
50 
6SE6400-5CA00-0BP0  
3.3.4.1 Commissioning 
with 
the 
Basic Operator Panel (BOP) 
 The Basic Operator Panel (BOP), which is available as an 
optional accessory, provides the user with access to the 
inverter parameters and enables you to customize the 
settings of your COMBIMASTER 411 & MICROMASTER 
411. The BOP is mounted in an Operator Panel Mounting 
Kit and connected to the COMBIMASTER 411 & 
MICROMASTER 411 via the serial interface (see Figure 
3-9). The BOP can be used to configure several 
COMBIMASTER 411 & MICROMASTER 411 Inverters. 
The BOP features a five-digit, seven-segment display for 
showing parameter numbers and values, alarm and fault messages and setpoints 
and actual values. Parameter sets cannot be saved via the BOP. 
Control functions for the inverter (ON/OFF, 
, reverse) are not active in the 
works settings. In order to specify this command via the BOP, P0700 = 1 must be 
set. 
If the BOP connection is removed during normal running the drives is stopped and 
the motor coasts to standstill. 
Table 3-5 shows the factory default settings for operation  via the BOP. 
Table 3-5 
Default Settings for BOP Operation 
Parameter Meaning 
Default 
Europe 
(North 
America) 
P0100 
Operating Mode Europe/US 
50 Hz, kW (60 Hz, hp) 
P0307 
Power (rated motor) 
kW (Hp) 
P0310 
Motor frequency rating 
50 Hz (60 Hz) 
P0311 
Motor speed rating 
1395 (1680) rpm [depending on variant]] 
P1082 
Maximum Motor Frequency 
50 Hz (60 Hz)