6  Troubleshooting 
MICROMASTER 411 & COMBIMASTER 411    Operating Instructions 
 
6SE6400-5CA00-0BP0 
85
 
No setpoint values from CB (communication board) during telegram off time 
Diagnose & Remedy  
Check CB and communication partner 
F0071  USS (BOP-link) setpoint fault 
OFF2 
Possible Causes 
No setpoint values from USS during telegram off time 
Diagnose & Remedy  
Check USS master 
F0072  USS (COMM link) setpoint fault 
OFF2 
Possible Causes 
No setpoint values from USS during telegram off time 
Diagnose & Remedy  
Check USS master 
F0080  ADC lost input signal 
OFF2 
Possible Causes 
 
Broken wire 
 
Signal out of limits 
F0085 External 
Fault 
OFF2 
Possible Causes 
External fault triggered via for example terminal inputs 
Diagnose & Remedy  
Disable for example terminal input for fault trigger 
F0090  Encoder feedback loss 
OFF2 
Possible Causes 
Signal from Encoder lost 
Diagnose & Remedy  
 
Check encoder fitted. If encoder not fitted, set P0400 = 0 and select SLVC mode (P1300 = 20 or 22) 
 
If encoder fitted, check correct encoder selected (check encoder set-up in P0400). 
 
Check connections between encoder and inverter 
 
Check encoder not faulty (select P1300 = 0, run at fixed speed, check encoder feedback signal in 
r0061) 
 
Increase encoder loss threshold in P0492 
F0101 Stack 
Overflow 
OFF2 
Possible Causes 
Software error or processor failure 
Diagnose & Remedy  
Run self test routines 
F0221  PID Feedback below min. value 
OFF2 
Possible Causes 
PID Feedback below min. value P2268 
Diagnose & Remedy  
 
Change value of P2268 
 
Adjust feedback gain 
F0222  PID Feedback above max. value 
OFF2 
Possible Causes 
PID feedback above max. value P2267 
Diagnose & Remedy