Справочник Пользователя для Siemens micromaster 411

Скачать
Страница из 164
6  Troubleshooting 
Issue 03/01 
 
MICROMASTER 411 & COMBIMASTER 411    Operating Instructions  
86 
6SE6400-5CA00-0BP0  
 
Change value of P2267 
 
Adjust feedback gain 
F0450  BIST Tests Failure 
OFF2 
Possible Causes 
Fault value  = 1:  Some power section tests have failed 
 
2:  Some control board tests have failed 
 
4:  Some functional tests have failed 
 
8:  Some IO board tests have failed (MM 420 only) 
 
16:  Internal RAM failed on power-up check 
Diagnose & Remedy  
Hardware defect, contact Customer Support / Service Department 
F0452  Belt Failure Detected 
OFF2 
Possible Causes 
Load conditions on motor indicate belt failure or mechanical fault. 
Diagnose & Remedy  
Check the following: 
 
No breakage, seizure or obstruction of drive train. 
 
If using an external speed sensor, check for correct function. Check parameters: 
P2192 (delay time for permitted deviation) 
 
If using the torque envelope, check parameters: 
P2182 (threshold frequency f1) 
P2183 (threshold frequency f2) 
P2184 (threshold frequency f3) 
P2185 (upper torque threshold 1) 
P2186 (lower torque threshold 1) 
P2187 (upper torque threshold 2) 
P2188 (lower torque threshold 2) 
P2189 (upper torque threshold 3 
P2190 (lower torque threshold 3) 
P2192 (delay time for permitted deviation)