6  Troubleshooting 
Issue 03/01 
 
MICROMASTER 411 & COMBIMASTER 411    Operating Instructions  
88 
6SE6400-5CA00-0BP0  
 
Load duty cycle must lie within specified limits 
 
Motor power (P0307) must match inverter power (r0206) 
A0511 Motor 
OverTemperature 
Possible Causes 
 
Motor overloaded 
 
Load duty cycle too high 
Diagnose & Remedy  
Independently of the kind of temperature determination check the following: 
 
Load duty cycle must be correct 
 
Motor nominal overtemperatures (P0626-P0628) must be correct 
 
Motor temperature warning level (P0604) must match 
If P0601 = 0 or 1, check the following: 
 
Check if name plate data are correct (if not perform quick commissioning) 
 
Accurate equivalent circuit data can be found by performing motor identification (P1910=1) 
 
Check if motor weight (P0344) is reasonable. Change if necessary 
 
Via P0626, P0627, P0628 the standard overtemperatures can be changed, if the motor is not a 
Siemens standard motor 
If P0601 = 2, check the following: 
 
Check if temperature shown in r0035 is reasonable 
 
Check if the sensor is a KTY84 (other sensors are not supported) 
A0522  I2C read out timeout 
Possible Causes 
The cyclic access to the UCE Values and powerstack temperatures via the I2C bus (MM440 Frame size 
FX & GX) is disturbed 
A0523 Output 
fault 
Possible Causes 
One motor phase is disconnected 
A0535  Braking Resistor Hot 
Diagnose & Remedy  
 
Increase duty cycle P1237 
 
Increase ramp down time P1121 
A0541  Motor Data Identification Active 
Possible Causes 
Motor data identification (P1910) selected or running 
A0542  Speed Control Optimisation Active 
Possible Causes 
Speed Control Optimisation (P1960) is selected or running 
A0590  Encoder feedback loss warning 
Possible Causes 
Signal from Encoder lost and Inverter has switched to sensorless vector control 
Diagnose & Remedy  
Stop inverter and then 
 
Check encoder fitted. If encoder not fitted, set P0400 = 0 and select SLVC mode (P1300 = 20 or 22) 
 
If encoder fitted, check correct encoder selected (check encoder set-up in P0400). 
 
Check connections between encoder and inverter 
 
Check encoder not faulty (select P1300 = 0, run at fixed speed, check encoder feedback signal in 
r0061) 
 
Increase encoder loss threshold in P0492