Allen-Bradley 160-Series AC Drives
F232120
40
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Power Terminal Block Description
Input and output power connections are performed 
through two separate terminal blocks. Refer to 
Figure 23.
Figure 23 
A-B 160 Power Block Terminal (TB1, TB2, 
GRD)
A-B 160 Torque Specifications
Table 24 
L1
R
L2
S
L3
T
BR
-
BR
+
T1
U
T2
V
T3
W
-
DC
+
DC
MOTOR
Ground Tab
Protected AC Input
Terminal Block Two (TB2) -
For Motor
Terminal Block Two (TB2) -
For Motor
Terminal Block One (TB1) -
For Line Power
Protected AC Input
Terminal Block One (TB1) -
For Line Power
FAULT
READY
MOTOR
R/
L1
S/
L2
T/
L3 BR- BR+
U/
T1
V/
T2
W/
T3 DC- DC+
Chassis
Chassis
160 Series C
160 Series A & B
FAULT
READY
R/L1
1 2 3 4 5 6 7 8 9 1011
S/L2 T/L3 BR- BR+
U/T1 V/T2 W/T3DC- DC+
U165ME3A
160 SERIES A & B
160 SERIES C
U165ME3A
Terminals
Description
GRD
Earth Ground
R, S, T (L1, L2, L3)
AC Input Line Terminals
BR+, BR-
Dynamic Brake Resistor 
Option – Refer to instructions 
with option
DC+, DC-
Capacitor Module Option
U, V, W (T1, T2, T3)
Motor Connection
Table 23 
Terminal
Screw 
Size
Max/Min Wire 
Size mm
2
 
(AWG)
Max/Min 
Torque 
N-m (lb-in)
TB1 & TB2 
Series A & B
M4
4/0.75
(12/18)
1.81/1.35
(16/12)
4.0 kW 
(7.5 HPDP)
Series C
M4
5.26 – 3.31
(10 – 12)
1.35 – 0.90 
(12 – 8)
All Other 
Ratings
Series C
M4
3.31 – 0.82 
(12 – 18)
1.35 – 0.90 
(12 – 8)