With the FT85081 transmitter/FR85081 receiver powered off, turn the Data Selection switch 
using a screwdriver until the number representing the required data communication is selected. 
Refer to Table A for Data Selection switch settings. 
Note the following:
The FT85081 transmitter/FR85081 receiver allows data translation between RS-232 and 
RS-422 signal levels. Consequently, the Data Selection switch can be set to 0 (RS-232) 
on the transmitter and to 1 (RS-422) on the receiver. Conversely, the Data Selection 
switch can be set to 1 (RS-422) on the transmitter and to 0 (RS-232) on the receiver.
If you wish to change the data communication setting after the FT85081 transmitter/
FR85081 receiver has been powered on, power off the transmitter/receiver, change the 
data communication setting, and then power on the transmitter/receiver again.
 
MOUNTING
 
The FT85081 transmitter/FR85081 receiver can be mounted into a rack or can be used as a 
standalone module. As a standalone module, the unit can be placed on a desktop or can be 
mounted to a wall.
 
NOTE:  
 
As a matter of convenience, it is recommended that you set the desired data 
communication before mounting the FT85081 transmitter/FR85081 receiver. To set the 
desired data communication, refer to the 
 
 
 
MOUNTING THE TRANSMITTER/RECEIVER INTO A RACK
 
The FT85081 transmitter/FR85081 receiver can be installed into the RK5000 Series rack mount 
chassis, which can be mounted into an industry-standard 19-inch (48.26 cm) equipment rack. 
The RK5000 Series rack mount chassis includes the following models:
 
RK5000PS-3U and RK5000-3U:  
 
Designed to accommodate fiber optic modules as 
follows:
The RK5000PS-3U rack mount chassis provides 12 single-width module slots and 
a power supply. 
The RK5000-3U rack mount chassis provides 14 single-width module slots (a 
power supply is not included). Power to the modules can be supplied using the 
optional external power supply (EPS5000-120).
For additional information, refer to the RK5000PS-3U/RK5000-3U Fiber Rack Mount 
Chassis Installation manual.
 
Table A.  
 
Data Selection Switch Settings
 
Data Selection
Switch Setting
 
RS-232
0 (default setting)
RS-422
1
RS-485 2-Wire
2
RS-485 4-Wire
3
Manchester/Bi-Phase
4
Not used
5-9