Справочник Пользователя для Honeywell ml6131

Скачать
Страница из 8
ML6131 DIRECT COUPLED ACTUATOR
63-2498—2
4
Preparation
Before mounting the actuator onto the shaft, determine the 
following:
1.
Size of the shaft (3/8 in. to 1/2 in.).
2.
Direction the shaft rotates to open the device (cw or 
ccw). See Fig. 3.
3.
Degrees of actuator stroke for opening device (45°, 60°, 
or 90°).
If the shaft is 3/8 in. round or square, use part number 201391 
Shaft Adapter provided inside the bag assembly shipped with 
the actuator. Place the adapter opposite the setscrews 
(see Fig. 4).
Fig. 3. Determining direction damper 
shaft rotates when opening.
Fig. 4. Using shaft adapter for 3/8 in. shafts.
Manual Operation (Declutch)
CAUTION
Personal Injury and Product Damage Hazard.
Do not use manual declutch without supporting 
the load.
Support load independent of actuator immediately 
prior to and while using manual declutch lever.
Manual declutch capability is available on some actuators. 
Use the manual declutch lever to manually adjust the actuator 
setting. Fig. 5 shows the location of the manual declutch lever. 
To operate, push the lever in the direction of the arrow on the 
lever cover.
Fig. 5. Location of manual declutch lever.
Installation
After determining the direction of the shaft rotation (cw or 
ccw), install the device. For valve linkage mounting, refer to 
the instructions shipped with the linkage. For damper 
mounting, proceed as follows:
1.
Place the actuator onto the damper shaft.
CAUTION
Equipment Damage Hazard.
Improper range stop selection can damage 
light-duty dampers.
Be sure to select the proper range stop.
2.
If the angle of the damper opening is either 45° or 60°, 
close the actuator using the manual declutch:
a. Disengage the hub using the declutch lever; see 
Manual Operation (Declutch) section.
b. Rotate the hub until the actuator gear train passes 
the proper 45° or 60° setting. (Do not insert the pin 
until after the actuator passes this point.)
c. Release the declutch lever.
NOTE:
Dampers with 90° stroke do not require the 
range stop pin.
3.
Insert the range stop pin into the appropriate (cw or 
ccw) 45° or 60° slot. The range stop pin is clipped into 
its final position only after the pin passes through both 
actuator plates (see Fig. 6). The range stop pin should 
snap into position and not be removable manually 
(see Fig. 7).
IMPORTANT
Do not fully tighten the mounting screw; the actuator 
must be allowed to float.
4.
With the actuator placed in its final position, secure the 
mounting tab to the damper box with a sheet metal 
screw.
5.
Position the damper in the open position and securely 
tighten the Allen screws into the damper shaft.
COOLING
AIR FLOW
COOLING 
AIR FLOW
CW TO OPEN, CCW TO CLOSE
CCW TO OPEN, CW TO CLOSE
M2067A
TYPE A DAMPER
TYPE B DAMPER
SHAFT ADAPTER
M2064
ML6131
M17611
DIRECT COUPLED ACTUATOR
ML6131
MANUAL 
DECLUTCH 
LEVER