Pin 17
 
(Amplitude/Power Regulation Status 
Output)
 
(Contact your sales representative about 
Power Regulation availability.)
 
This status signal is most useful when the power regula-
tion mode is selected. This Out of Regulation status signal 
would indicate that due to inadequate pressure against the 
ultrasonic horn, the power regulation level setting can 
not be achieved when the amplitude level is set to the 
maximum level of 100%.
In the amplitude regulation mode, this signal will be 
activated at the end of the ramp-up time until the begin-
ning of the ramp-down time. This status signal will be 
active for the time the ultrasound is at the programmed 
amplitude setting.
Pin 17 is a digital active low status output that activates 
when the system is regulating the amplitude or power 
level correctly. This output becomes an open circuit when 
the system falls out of regulation. When that happens, it 
cannot adjust the system output to the output level that 
was programmed as the regulation set point.
Pin 18
 
(Not Used)
Pin 19
 
(System Power OK Status Output)
Pin 19 is a digital active low status output that activates 
when no fault conditions are detected by any of the power 
fault detection circuits included in the system. This output 
will be an open circuit when any power related fault is 
detected in the system.
Pin 20
 
(Bad Part Status Output)
 
Pin 20 is a digital active low status output that activates, 
either momentarily or until the start of the next welding 
cycle, when the welding parameters recorded during the 
previous welding cycle are outside of the programmed 
bad part limits. This output will be an open circuit when 
a bad part has not been detected.
Pin 21
 
(Good Part Status Output)
Pin 21 is a digital active low status output that activates, 
either momentarily or until the start of the next welding 
cycle, when the welding parameters recorded during the 
previous welding cycle do not exceed the programmed 
suspect or bad part limits. This output will be an open 
circuit after a welding cycle when either a suspect or bad 
part has been detected.
Pin 22
 
(System Ready Status Output)
This status output signal will activate only when the system 
is ready to activate ultrasound or begin a weld cycle. Pin 
22 is a digital active low status output that activates when 
a weld processing cycle is completed and the welding 
process control system is ready to start the next welding 
cycle. This output will be an open circuit when the welding 
process controller determines that the next welding cycle 
cannot be started. This includes system faults or off line 
active, but not a process fault like Overload.
Continued from previous page
Pin 23
 
(Suspect Part Status Output)
Pin 23 is a digital active low status output that activates, ei-
ther momentarily or until the start of the next welding cycle, 
when the welding parameters recorded during the previous 
welding cycle are outside of the programmed suspect part 
limits. This output will be an open circuit after a welding 
cycle when a suspect part has not been detected.
Pin 24
 
(Isolated Common)
Pin 24 is electrically isolated from chassis ground. This 
common line should be connected to negative output at a 
user-provided isolated 24VDC power supply. The isolated 
NPN status output signals can drive PNP inputs.
Pin 25
 
(Not Used)
Pin 25 is an open connection.
Page 26 
iQ  Series
 Ultrasonic Generator/Power Supply ES User’s Manual
Dukane Manual Part No. 403-575-00