Selection of operation mode and operation location
4.18.3 Start command source and frequency command source during communication 
operation (Pr. 338, Pr. 339, Pr. 551)
(1) Selects the command source of the PU operation mode (Pr. 551)
Any of the operation panel, PU connector can be specified as the command source in the PU operation mode.
In the PU operation mode, set Pr. 551 to "2" when executing parameter write, start command or frequency command
during the RS-485 communication with PU connector.
PU...PU operation mode, NET...network operation mode, —...without command source
∗1
The Modbus-RTU protocol cannot be used in the PU operation mode. When using the Modbus-RTU protocol, set Pr. 551  
≠ "2".
∗2
When Pr. 551 = "9999", the priorities of the PU control source is parameter unit (FR-PU04/FR-PU07) 
> operation panel. 
When the RS-485 communication with the PU connector is used, the external start command and frequency command
can be made valid. Command source in the PU operation mode can be selected.
From the communication device, parameter unit, etc. which have command source, parameter write or start command
can be executed. Parameter read or monitoring can be executed in any operation mode.
Parameter 
Number
Name
Initial 
Value
Setting 
Range
Description
338
Communication operation 
command source
0
0
Start command source communication
1
Start command source external
339
Communication speed 
command source
0
0
Frequency command source communication
1
Frequency command source external
2
Frequency command source external (Frequency command from 
communication is valid, frequency command from terminal 2 is 
invalid)
551
 ∗
PU mode operation 
command source 
selection
9999
2
PU connector is the command source when PU operation mode.
4
Operation panel is the command source when PU operation mode.
9999
Parameter unit automatic recognition
Normally, operation panel is the command source. When the 
parameter unit is connected to the PU connector, PU is the 
command source. 
The above parameters can be set when Pr. 160 Extended function display selection = "0". (Refer to page 162)
Pr. 551 is always write-enabled.
Pr. 551
Setting
Command Source
Remarks
Operation 
panel
Parameter 
unit
RS-485 
communication
2
PU
PU
 ∗1
Switching to NET operation mode 
disabled
4
PU
NET
9999
(initial value)
PU
PU
 ∗2
NET
NOTE
When performing the RS-485 communication with the PU connector when  Pr. 551 = "9999", PU mode command
source does not automatically change to the PU connector. 
When Pr. 551
 = "2" (PU mode PU connector), the operation mode cannot be switched to the network operation mode.
Changed setting value is valid when powering on or resetting the inverter.
The Modbus-RTU protocol cannot be used in the PU operation mode. Select network operation mode (NET mode
command source).