Справочник Пользователя для Mitsubishi Electronics FR-D740-012

Скачать
Страница из 294
89
Frequency setting by external terminals
4.6 Frequency setting by external terminals
4.6.1
Operation by multi-speed operation (Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr. 239)
The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter write selection.
* The above parameters can be set when Pr. 160 Extended function display selection = "0". (Refer to page 162)
Purpose
Parameter that should be Set
Refer to Page
Make frequency setting by 
combination of terminals
Multi-speed operation
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Perform Jog operation
Jog operation
Pr. 15, Pr. 16
Infinitely variable speed setting by 
terminals
Remote setting function
Pr. 59
Can be used to change the preset speed in the parameter with the contact signals.
Any speed can be selected by merely turning on-off the contact signals (RH, RM, RL, REX signals).
Parameter 
Number
Name
Initial Value
Setting Range
Description
4
Multi-speed setting (high 
speed)
60Hz
0 to 400Hz
Frequency when RH turns on
5
Multi-speed setting (middle 
speed)
30Hz
0 to 400Hz
Frequency when RM turns on
6
Multi-speed setting (low 
speed)
10Hz
0 to 400Hz
Frequency when RL turns on
24
 ∗
Multi-speed setting (speed 4)
9999
0 to 400Hz, 9999
Frequency from 4 speed to 15 speed can 
be set according to the combination of 
the RH, RM, RL and REX signals.
9999: not selected
25
 ∗
Multi-speed setting (speed 5)
9999
0 to 400Hz, 9999
26
 ∗
Multi-speed setting (speed 6)
9999
0 to 400Hz, 9999
27
 ∗
Multi-speed setting (speed 7)
9999
0 to 400Hz, 9999
232 
Multi-speed setting (speed 8)
9999
0 to 400Hz, 9999
233
 ∗
Multi-speed setting (speed 9)
9999
0 to 400Hz, 9999
234
 ∗
Multi-speed setting (speed 10)
9999
0 to 400Hz, 9999
235
 ∗
Multi-speed setting (speed 11)
9999
0 to 400Hz, 9999
236
 ∗
Multi-speed setting (speed 12)
9999
0 to 400Hz, 9999
237
 ∗
Multi-speed setting (speed 13)
9999
0 to 400Hz, 9999
238
 ∗
Multi-speed setting (speed 14)
9999
0 to 400Hz, 9999
239
 ∗
Multi-speed setting (speed 15)
9999
0 to 400Hz, 9999
(1) 3-Speed setting (Pr. 4 to Pr. 6)
The inverter operates at frequencies set in Pr. 4 when RH signal is on,
Pr. 5 when RM signal is on and Pr. 6 when RL signal is on.
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
Output frequency (Hz)
Speed 1
(High speed)
Speed 2
(Middle speed)
Speed 3
(Low speed)
Speed 4
Speed 5
Speed 6
Speed 7
RH
RM
RL
Time
REMARKS
In the initial setting, if two or three of multi-speed settings are simultaneously selected, priority is given to the set frequency of
the lower signal.
For example, when the RH and RM signals turn on, the RM signal (Pr. 5) has a higher priority.
The RH, RM, RL signals are assigned to the terminal RH, RM, RL in the initial setting. By setting "0 (RL)", "1 (RM)", "2 (RH)" in
any of Pr. 178 to Pr. 182 (input terminal function selection), you can assign the signals to other terminals.