Understanding LED Indications
Figure 9 shows the NI 9144 chassis LEDs.
Figure 9.  NI 9144 Chassis LEDs
POWER LED
The POWER LED is lit while the NI 9144 chassis is powered on. This LED 
indicates that the power supply connected to the chassis is adequate.
FPGA LED—Open FPGA Mode Only
This LED is for Open FPGA mode only. This mode is currently not 
activated.
RUN and ERR LEDs
The RUN LED is green and indicates that the NI 9144 is in an operational 
state. The ERR (error) LED is red and indicates error codes. Table 1 lists 
the RUN and ERR LED indications.
Table 1.  RUN and ERR LED Indications
LED 
Behavior
RUN LED
ERR LED
Run Mode
Description
Error Mode
Description
Off
INIT (Initialize)
Slave discovery and 
Initialization
No Error
Blinking
PRE-OP
(Pre-Operational)
Module detection, 
configuration, and 
synchronization
Invalid 
Configuration
Unsupported 
Module, Bad 
Device Profile, 
Object Dictionary, 
and configuration
Single-Flash
SAFE-OP
(Safe 
Operational)
Inputs are 
functional, outputs 
drive constant safe 
values
Unsolicited 
State Change
Backplane or 
Module 
emergency 
condition
POWER
FPGA
RUN
ERR