NI 9144 User Guide and Specifications
NI 9264
NI 9264 Calibration Data
The NI 9263 has four channels with a nominal range of ±10.5 V. Each 
channel has an associated LSB weight, which is the number of volts per bit, 
and an offset, which is the number of volts per bit measured when the inputs 
are grounded.
Note
LSB weight is referred to as Gain in the object dictionary.
The calibration data is stored in a U32 array, though each Offset field 
(subindex 1, 3, 5, and so on) should be interpreted as a signed value.
Use the calibration coefficients with the following equation to generate 
corrected data:
Table 58.  NI 9264 Vendor Configuration Extensions
Index
Sub
Type
R/W
Description
0x2100
1
ARR:U32
Calibration = 16
2
R
Ch0 Gain
3
R
Ch1 Offset
...
...
...
8
R
Ch3 Gain
9
R
External Ch0 
Offset
...
...
...
Table 59.  NI 9264 Scan List Format
Coefficient
Representation
Units
LSB Weight
Unsigned
pV/LSB
Offset
Signed
nV
V
desired
Code
(
)
Code LSB
weight
nV
bits
---------
⎞ 10
9
V
nV
-------
⎞ Offset nV
(
) 10
9
V
nV
-------
+
=