SCC-CO20 Isolated Current Output Module User Guide
Using an External Loop Supply
In order for the current sink to operate properly with an external loop 
supply, the voltage must be within the range of 3 to 42 V. If the voltage is 
too high, overheating can occur and damage the module. Figure 4 shows 
four configurations using an external loop supply.
Figure 4.  Connecting the SCC-CO20 Using an External Loop Supply
When you use an external loop supply, the order of the supply and load does 
not matter as long as you do not create a second loop through which current 
flows. If both the supply and the load are grounded, connect the signals as 
shown in Figure 5.
High 
CMV 
High 
CMV
Load 
SINK 
– 
SCC-CO20 
ISO GND 
a. Nonreferenced load and external voltage supply (two circuits) 
b. Referenced load and external voltage supply (two circuits) 
Load 
SINK 
– 
SCC-CO20 
ISO GND 
Load 
SINK 
– 
SCC-CO20 
ISO GND 
Load 
SINK 
– 
SCC-CO20 
ISO GND 
– 
– 
0–20 mA 
0–20 mA 
0–20 mA 
0–20 mA