Installation Guide – DOC. 6413A 
iLux
 Lighting Systems:  CLSI-C6 & CLSI-C6M  
  3  
 
5.  Connect each load wire to the corresponding 
LOAD terminals on the unit, connect the power 
line hot wire from the circuit breaker to the HOT 
terminal on the unit, connect all neutral wires to 
the NEUTRAL terminal on the unit, and connect 
all ground wires to the   (ground) terminal on 
the unit.  
6.  If Cresnet cabling is part of the installation, 
attach the supplied terminal block connector(s) 
to the Cresnet cable(s) and plug into the 
appropriate port(s) on the unit. Make certain that 
there is a minimum 1/4-inch (0.6 cm) separation 
between the Class 2 Cresnet wiring and the Class 
1 AC wiring.  
7.  Carefully tuck all wires into the wallbox and 
fasten the unit to the wallbox using the four  
7/8-inch Phillips screws supplied. 
8.  Reattach the control panel overlay to the front 
panel by inserting the four tabs into the slots 
provided, and install the hinged front cover 
assembly by lining it up at the top and pressing 
the bottom edge until it snaps into position. 
 
Power up and Testing 
The following illustration shows the front panel of the 
unit and the controls used during installation. 
Front Panel Controls and Indicators 
^^
Scene 1
Scene 2
Scene 3
Scene 4
Scene 5
Scene 6
^^
Min
Sec
Lights
Shades
Save
Cancel
1
2
3
4
5
6
ON
OFF
LED
Bargraphs
Two-Digit
Display
Function
Buttons
 
 
 
 
 
Verify the basic installation and wiring connections as 
follows: 
1. Press 
the 
Lights button to enable manual light 
control, and press the right side and the left side 
of each of the function buttons to increase and 
decrease the lighting level of those loads. Verify 
that the intended loads and corresponding LED 
bargraphs respond appropriately. 
2. Press 
the 
OFF button to turn off all loads. The 
loads will ramp down to off while the two-digit 
display counts down to off (blank). Two seconds 
after all lights have turned off, the unit’s master 
air-gap relay opens making it safe to service the 
lighting installations.  
 
 
 
 
LOAD 3
LOAD 2
LOAD 1
HOT
NEUTRAL
Distribution
Panel
LOAD 4
LOAD 5
LOAD 6
10A or 13A
Circuit
Breaker
A/R