FlipTop Media Center 
 
 
Crestron QM-FTMC 
 
SETUP LED and Pushbutton 
The QM-FTMC is Touch-Settable ID-ready. A SETUP pushbutton and 
associated LED are located on the bottom of the unit next to the Cresnet 
connectors. The SETUP pushbutton and its associated LED are used for setting 
a units network ID during the initial configuration of a Cresnet system or when 
the device is being added/replaced.  
Industry Compliance 
As of the date of manufacture, the QM-FTMC has been tested and found to 
comply with specifications for CE marking and standards per EMC and 
Radiocommunications Compliance Labelling.  
          
 
NOTE:  This device complies with part 15 of the FCC rules. Operation is 
subject to the following two conditions: (1) this device may not cause harmful 
interference, and (2) this device must accept any interference received, including 
interference that may cause undesired operation.  
Setup 
Network Wiring 
CAUTION:  In order to ensure optimum performance over the full range of 
your installation topology, Crestron Certified Wire, and only Crestron Certified 
Wire, may be used. Failure to do so may incur additional charges if support is 
required to identify performance deficiencies as a result of using improper wire. 
CAUTION:  Use only Crestron power supplies for Crestron equipment. Failure 
to do so could cause equipment damage or void the Crestron warranty. 
CAUTION:  Provide sufficient power to the system. Insufficient power can lead 
to unpredictable results or damage to the equipment. Please use the Crestron 
Power Calculator to help calculate how much power is needed for the system 
(
http://www.crestron.com/calculators
).
 
When calculating the length of wire for a particular Cresnet run, the wire gauge 
and the Cresnet power usage of each network unit to be connected must be taken 
into consideration. Use Crestron Certified Wire only. If Cresnet units are to be 
daisy-chained on the run, the Cresnet power usage of each network unit to be 
daisy-chained must be added together to determine the Cresnet power usage of 
the entire chain. If the unit is a home-run from a Crestron system power supply 
network port, the Cresnet power usage of that unit is the Cresnet power usage of 
the entire run. The wire gauge and the Cresnet power usage of the run should be 
used in the following equation to calculate the cable length value on the 
equation’s left side. 
Cable Length Equation 
40,000
Where:  
R x P
L <
L = Length of run (or chain) in feet.                                        
R = 6 Ohms (Crestron Certified Wire: 18 AWG (0.75 MM
2
))  
P = Cresnet power usage of entire run (or chain).
 
14 
 FlipTop Media Center: QM-FTMC 
 
Operations & Installation Guide - DOC. 6311A