Terminal Block & Module   
Crestron CLT- & CLX-1FAN4
 
Wiring Diagram of the Terminal Block to the Feed and 
Load(s) (Single-wide and Left Side Double-wide Enclosures) 
NOTE:  Unless otherwise indicated, the lighting 
system specified in this guide is modular, requiring 
assembly in the field by a licensed electrician, in 
accordance with all national and local codes. 
TERMINAL
BLOCK
N OUT 2
GROUNDING
TERMINAL
BLOCK
GND
CRESTRON
LEFT SIDE
WIRING LABEL
TO
LOAD(S)
AREA FOR
MODULE
LOCATION
LABEL
N OUT 3
N OUT 4
(FROM 15 OR 20 AMP 
CIRCUIT BREAKER)
NEUTRAL
HOT
FAN 1
FAN 3
N IN
N OUT 1
FAN 4
FAN 2
LINE
120VAC 60 Hz
8A MAX
2A MAX/CKT
1 FEED
4 FAN
CLX-1FAN4
 
If you require a UL Listed panel, Crestron offers this 
service through its UL Listed panel shop. This 
includes complete in factory system configuration 
and assembly by Crestron for an additional fee.  
Terminal Block Installation and Field 
Wiring 
1.  Use the two supplied self-tapping pan Phillips 
screws (8B x ¼ length) to secure the terminal 
block and the appropriate (left or right) wiring 
label to the Crestron Automation Enclosure. The 
wiring label lies beneath the terminal block as 
shown in the two wiring diagrams on this page. 
NOTE:  Both left and right wiring labels are 
provided. The left-side labels are common for both 
single and double-wide enclosures. The right-side 
labels are only used in double-wide enclosures since 
the modules and terminal blocks along the right side 
must be inverted when mounting.  
Wiring Diagram of the Terminal Block to the Feed and 
Load(s) (Right Side Double-wide Enclosures) 
NEUTRAL
(FROM 15
OR 20 AMP
CIRCUIT
BREAKER)
TERMINAL
BLOCK
AREA FOR
MODULE
LOCATION
LABEL
RIGHT SIDE
WIRING LABEL
CRESTRON
TO
LOAD(S)
GROUNDING
TERMINAL
BLOCK
HOT
120VAC 60 Hz
8A MAX
2A MAX/CKT
GND
1 FEED
CLX-1FAN4
4 FAN
N OUT 4
N OUT 3
N OUT 2
N OUT 1
N IN
FAN 4
FAN 3
FAN 2
FAN 1
LINE
 
NOTE:  Use copper conductors only – rated 75
°C 
2.  With the circuit breaker turned off, connect the 
circuit feed (HOT and NEUTRAL) and 
controlled circuit (LOAD) wires to the terminal 
block per the markings provided on the wiring 
label (as shown in the two wiring diagrams on 
this page). Terminal blocks accept one 14 - 10 
AWG wire. Wires should be stripped to ½ inch. 
Tighten terminal blocks to 9 in-lbs. Do not over 
tighten.  
NOTE:  Only one fan may be wired per circuit. 
3.  Grounding terminal blocks are available in the 
cabinet for termination of ground wires. Tighten 
to 35 in-lbs. (14 – 10 AWG), 40 in-lbs.  
(8 AWG), or 45 in-lbs. (6 – 4 AWG).  
 
 
2  
  Terminal Block & Module:  CLT- & CLX-1FAN4 
Installation Guide – DOC. 6032A