Chapter 3
Example Applications
3-12
©
 National Instruments Corporation
In the case of Analog Output blocks, you do not need to tell the block to use 
the scaling parameters. The block will always use both 
XD_SCALE
 and 
PV_SCALE
 parameters.
Set Up Scheduling
Before the block will operate, you need to schedule the block to execute. 
All Fieldbus function blocks (including function blocks on the FP-3000) 
execute according to a schedule. You can specify the order of function 
blocks in the schedule and the rate at which the schedule is repeated. To 
make the configurator create a schedule for your block, complete the 
following steps:
1.
Double-click on Function Block Application in the tree view of the 
configurator.
2.
Drag the block from the tree view to the application view. The 
configurator automatically generates a schedule for the block that 
causes it to run every second (refer to the documentation that came 
with your configurator for information about changing the execution 
period).
3.
To download this schedule to the device, select Configure»Download 
Configuration
. A dialog box appears that enables the configuration to 
be downloaded. Go through the download process as described in the 
documentation that came with your configurator. Since the block is not 
scheduled when you start the download, its actual mode does not 
change until the download is complete.
Bring the Block Online
1.
Go to the 
MODE_BLK
 parameter and set the 
TARGET
 to 
Auto
2.
Re-read the 
MODE_BLK
 parameter. The 
ACTUAL
 field should go to 
Auto
. If it does not, refer to Appendix C, 
, for 
more information.
Once the block goes to 
Auto
, it is fully operational. You can adjust the Set 
Point by writing a value between 0 and 100 to SP. The current flow through 
the heating element will vary.
If you are only interested in making FP-3000 output current and not 
interested in closed loop control, you are finished with this example.