Chapter 3
Example Applications
©
 National Instruments Corporation
3-13
PID Control
Instantiate a PID Block
Now that your input and output blocks are functioning, you can “close the 
loop” by creating a control block and putting the loop under automatic 
control. To instantiate a PID block, follow these steps:
1.
Right-click on FP-3000 in the configurator.
2.
Select Instantiate New Block. This causes a dialog box to appear that 
lists all of the blocks supported by the FP-3000 and allows them to be 
instantiated.
3.
Select Proportional Integral Derivative Block from the list, then 
click on the OK button. 
Assign a Tag to the New Block
By default, new blocks are created without a tag. To assign a tag, follow 
these steps:
1.
Right-click on Proportional Integral Derivative Block, then select 
Set Tag
2.
Enter the tag you choose in the dialog box. The tag can be up to 
32 characters in length and should not contain the dot (“.”) character.
3.
Click on OK.
Scale the PID
The PID has a 
PV_SCALE
 for scaling its input. The 
PV_SCALE
 should 
match the output scale (
OUT_SCALE
) of the AI block. To set the PID, enter 
the following:
PV_SCALE
EU at 100%
1775
EU at 0%
-273
Units Index °C
Decimal
2
The AO block takes a percentage range from the controller of 0 to 100 
percent, so adjust the PID block to output that range. To set the 
OUT_SCALE
 
parameter of the PID, enter the following:
OUT_SCALE
EU at 100%
100
EU at 0%
0
Units Index %
Decimal
2