Chapter 4
Block Reference
©
 National Instruments Corporation
4-15
FP_AO_200_RANGE
Allows the range of a channel on a FieldPoint FP-AO-200 to be adjusted.
FP_CJC_SOURCE 
Allows the cold junction compensation to be adjusted on a FP-TC-120 
module. 
Note
Cold junction compensation is global to the entire module and affects every channel 
on the module.
FP_MOD_STATUS 
The status of the FieldPoint I/O module associated with the function block.
FP_NOISE_REJECTION
Allows the noise rejection filter of an Analog Input module to be adjusted.
Table 4-10.  Module Status
Status
Description
No Base
There is no terminal base in the specified 
module position.
Base, But No Module
There is a terminal base in the specified 
module position, but no module is installed 
in the base.
Unconfigured Module
There is a module in the specified position, 
but the FP-3000 is unable to configure it.
Module in 
Configuration
There is a module in the specified position, 
the FP-3000 has attempted to configure the 
module, and the module is in the process of 
configuration.
Module Okay
There is a module in the specified position, 
and it is configured and operating correctly.
Incorrect Module 
for Block
There is a module in the specified position, 
but the block is incompatible with the 
module.