Справочник Пользователя для National Instruments FP-3000

Скачать
Страница из 118
Chapter 4
Block Reference
©
 National Instruments Corporation
4-13
FP-3000 Specific Parameters
CFG_OPTS
An option in the I/O function blocks to automatically set the scaling or alter 
the block behavior. Generally, this option can make configuration easier.
DEV_OPTS
A list of device-wide options that can be turned on and off at will. The 
current firmware supports only one option.
EXECUTION_STATISTICS
A repository containing performance statistics for a given block. Use 
EXECUTION_STATISTICS
 to asses the performance of a given 
configuration and allow appropriate changes to be made.
Table 4-7.  Configuration Options
Option
Description
Automatically Adjust 
XD_SCALE
Enabling this option allows the block to 
automatically determine its 
XD_SCALE
 
parameter, based on the physical I/O channel 
range, which is set by parameters such as 
FP_AI_100
 range.
Ignore Unconnected 
Interlock Inputs
By default, all interlock inputs on the CDO 
block must be good, or the block enters fault 
state. Enabling this option allows inputs with 
a status of 
Bad::Not_Connected
 to be 
ignored.
Table 4-8.  Device Options
Options
Description
Disable 
CFG_OPTS
 in all 
I/O blocks
This bit disables all block configuration 
options in 
CFG_OPTS
. It is not 
recommended that this bit be set since the 
additional behavior can make configuration 
easier.