Appendix C
Fieldbus Parameters
C-14
©
 National Instruments Corporation
NV_CYCLE_T
The time interval in milliseconds in which nonvolatile parameters are 
committed to nonvolatile storage.
Table C-9.  Operational Modes
Mode
Description
Target
The desired mode of operation of the block.
Out of Service (
O/S
). The block is out of service, block execution is suspended, 
and all output parameters take a status of 
Bad::OutOfService
.
Initialization Manual (
IMan
). The block is in the process of initializing a cascade. 
This is used for upstream (control) blocks when they are initializing for smooth 
transfer into 
Automatic
 mode.
Local Override (
LO
). Faultstate or an interlock is active and causing the output 
value of the block to be overridden.
Manual (
Man
). The output value of the block is set by the user.
Auto (
Auto
). The output value of the block is set by the block to be equivalent to 
the setpoint (SP) parameter of the block.
Cascade (
Cas
). The setpoint for the block is taken from the 
CAS_IN
 parameter. 
This mode cannot be entered before cascade initialization takes place.
Remote Cascade (
RCas
). Like Cascade mode, in Remote Cascade mode the 
setpoint of the block comes from an outside data source. Unlike Cascade mode, 
in Remote Cascade mode the setpoint is sourced from the 
RCAS_IN
 parameter, 
which is written by a host application and not another function block.
Remote Output (
ROut
). Remote Output mode is analogous to Remote Cascade 
mode, except that the remote host application directly sets the output of the block 
and not the setpoint. In the case of an analog output block, this bypasses setpoint 
rate and absolute limiting.
Actual
A bit reflecting the current state of operation of the block. This is a function of 
the target mode and the current conditions in which the block is executing.
Permitted
A bitmask indicating which modes are permitted target modes and which are not. 
This could be used by the plant operator to disallow certain modes the block 
would normally be permitted to have as a target mode.
Normal
Not used by the block, this can be used by an operator to store the normal mode 
of operation for the block in normal plant operations.