Appendix C
Fieldbus Parameters
©
 National Instruments Corporation
C-15
OP_CMD_CXO
The lowest level priority input. This can be used to allow the operator to 
activate interlock behavior with a write from the host application.
OUT
The current output value of the block.
OUT_HI_LIM
A limit for the maximum output value from a block in modes other than 
manual.
OUT_LO_LIM
A limit for the minimum output value from a block in modes other than 
manual.
OUT_SCALE
The scaling parameter used for the output parameter.
Table C-10.  Command Parameters
Value
Description
Close
When this flag is set, the output of the block is forced to 
Discret_State_0
. This interlock is overridden by every other 
interlock. If both 
OP_CMD_CXO.Close
 and 
OP_CMD_CXO.Open
 are 
set, they are both considered to be clear.
Open
When this flag is set, the output of the block is forced to 
Discret_State_1
. This interlock is overridden by every other 
interlock. If both 
OP_CMD_CXO.Close
 and 
OP_CMD_CXO.Open
 are 
set, they are both considered to be clear.
Stop
Unused in FieldPoint.
Enable 1, 2 ,3
Unused in FieldPoint.