Справочник Пользователя для National Instruments FP-3000
Appendix C
Fieldbus Parameters
©
National Instruments Corporation
C-21
STRATEGY
Used to identify groupings of blocks.
TAG_DESC
Used to describe the purpose of the block.
TEST_RW
Unused by the block algorithm. Used to test interoperability of reads and
writes of different parameter types.
writes of different parameter types.
TRK_IN_D
Used to enable tracking of the output value to
TRK_VAL
. When this is true,
the output value of the block takes on the value specified in
TRK_VAL
.
TRK_SCALE
The scaling parameter used for the value specified by
TRK_VAL
.
TRK_VAL
The track value of the block when tracking is enabled.
Bad if Limited
Produce an output status of
Bad
if the transducer value is
limited.
Uncertain if Manual Mode
Set the output status of the block to
Uncertain
if the block
is in manual mode.
Do Not Select if Not
Auto
Mode
Set the output status of the block to
Do Not Select
if the
block is not in an actual mode of
Auto
. This is useful for
blocks upstream of the selector block.
Do Not Select if Not
Cas
Mode
Set the output status of the block to
Do Not Select
if the
block is not in an actual mode of
Cas
. This is useful for blocks
connected to a selector block.
Table C-15. Status Options (Continued)
Option
Meaning