Appendix C
Fieldbus Parameters
C-22
©
 National Instruments Corporation
UPDATE_EVT
The current state of the update event, along with a time and date stamp. This 
event is issued whenever a static parameter is changed and 
ST_REV
 is 
incremented.
WRITE_ALM
The current state of the low alarm, along with a time and date stamp.
WRITE_LOCK
The software write lock for the device. When this is set to true, writes to all 
configuration parameters of all blocks are disallowed. The 
WRITE_ALM
 
block alarm is active when writes are allowed and clear when they are 
disallowed.
WRITE_PRI
The priority of the write alarm.
XD_SCALE
The scaling parameter used to interpret values from the physical I/O 
channel. This is used to translate from a physical transducer value to a 
percent of scale.
Table C-16.  Scaling Parameter Values
Subfield
Meaning
EU_100
Engineering units value at 100 percent of scale.
EU_0
Engineering units value at zero percent of scale.
UNIT_INDEX
Actual engineering units code (such as mA).
DECIMAL
Number of digits a host shows to the right of the 
decimal for display purposes.