Справочник Пользователя для National Instruments FP-3000

Скачать
Страница из 7
© National Instruments Corp.
5
FP-3000
Powering the FP-3000
Caution
Connect the FP-3000 to the terminal base before 
applying power to the FP-3000 to avoid damaging the 
FP-3000 or a terminal base. 
An 11-30 VDC power supply is required by each FP-3000 on your 
network. The FP-3000 filters and regulates this supplied power and 
provides power for all the I/O modules in the bank. Therefore, you 
do not need to provide power separately to each FieldPoint I/O 
module in the bank. If your field I/O devices need to be powered 
separately, you can use the terminals provided on each terminal 
base for such power supply connections.
The power connector is a 6-pin screw terminal connector whose 
pinout is shown in Figure 6.
Figure 6.  FP-3000 Power Connector Pinout
Connect the primary power supply to the center V and C pair. You 
can connect an optional backup power supply to the left V and 
C pair. The right V and C pair provides a convenient means of 
connecting power to the V and C terminals of a terminal base. 
Figure shows this optional connection.
Specifications
FP-3000............................................. FOUNDATION Fieldbus H1
Integrity............................................. Checksum
Power supply range........................... 11 to 30 VDC
Maximum terminal bases/bank......... 9
v
v
v
c c
c
11-30 VDC
Backup Power
Supply
(optional)
+
+
11-30 VDC
Primary Power
Supply
V
C
To adjacent device
(optional connection)