UB10.241 
 
  USeries 
24V, 10A, DC-UPS 
 
 
 
18.  E
NVIRONMENT
 
 
Operational temperature 
-25°C to +70°C (-13° to +158°F) 
For the DC-UPS control unit. 
 
Keep battery in a cooler environment! 
+60°C to +70°C  (+140°F to +158°F), 
 Derating 
0.43A/°C 
normal mode see Fig. 18-1
+60°C to +70°C  (+140°F to +158°F), 
  
0.25A/°C 
buffer mode see Fig. 18-2
  Storage temperature 
-40 to +85°C (-40° to +185°F) 
Storage and transportation, except battery 
Humidity 
5 to 95% r.H. 
IEC 60068-2-30 
Do not energize while condensation is present 
 
  Vibration sinusoidal 
2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g 
IEC 60068-2-6 
  Shock 
30g 6ms, 20g 11ms 
IEC 60068-2-27 
  Altitude 
0 to 6000m 
Approvals apply only up to 2000m 
  Over-voltage category 
III 
EN 50178 
   
II 
EN 50178   above 2000m altitude 
16/23 
  Degree of pollution 
EN 50178, not conductive 
 
 
Fig. 18-1   Output current vs. ambient temperature 
 
Fig. 18-2   Output current vs. ambient temperature 
Allowable  Output
Current in Normal Mode
0
-25
0
20
40
70°C
2.5
5
7.5
10
12.5
15A
continuous
60
Ambient Temperature
Allowable Output
Current in Buffer Mode
0
-25
0
20
40
70°C
2.5
5
7.5
10
12.5
15A
continuous
60
Ambient Temperature
for typ. 5s
 
 
 
 
The ambient temperature is defined 2cm below the unit. 
 
 
19.  P
ROTECTION 
F
EATURES
 
 
 Output 
protection 
Electronically protected against overload, no-load and short-circuits 
  Output over-voltage protection 
in buffer mode 
typ. 32Vdc 
max. 35Vdc 
In case of an internal defect, a redundant circuitry 
limits the maximum output voltage. The output 
automatically shuts-down and makes restart attempts. 
  Degree of protection 
IP20 
EN/IEC 60529 
  Penetration protection 
> 3.5mm 
E.g. screws, small parts 
  Reverse battery polarity protection 
yes 
Max. –35Vdc;  
  Wrong battery voltage protection 
yes 
Max. +35Vdc  (e.g. 24V battery instead of 12V battery) 
  Battery deep discharge protection 
yes 
The limit is battery current dependent 
  Over temperature protection 
yes 
Output shut-down with automatic restart 
 Input 
over-voltage 
protection 
yes 
Max. 35Vdc, no harm or defect of the unit 
 Internal 
input 
fuse 
25A, 
blade type 
No user accessible part, no service part 
June. 2010 / Rev. 1.3  DS-UB10.241-EN 
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time  
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current. 