Техническое Руководство для Puls ML60.121 Power Supply

Скачать
Страница из 23
 
 
ML60.121
 
 
MiniLine-2 
 
12V,
 
4.5A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
17.  D
IELECTRIC 
S
TRENGTH
 
The output voltage is floating and has no ohmic connection to the ground. Type and factory tests are conducted by 
the manufacturer. Field tests may be conducted in the field using the appropriate test equipment which applies the 
voltage with a slow ramp (2s up and 2s down). Connect all phase-terminals together as well as all output poles before 
conducting the test. When testing, set the cut-off current settings to the value in the table below. 
 
 
Fig. 17-1   Dielectric strength 
 
 
 
A B C 
Type test 
60s 
2500Vac 
4000Vac 
2000Vac 
Factory test 
5s 
2500Vac 
2500Vac 
500Vac 
Field test 
5s 
2000Vac 
2000Vac 
500Vac 
Cut-off current setting 
> 4mA 
> 4mA 
> 1mA 
 
A
N
L
Input
Earth, PE
Output
 -
+
B
 
 
 
To fulfill the PELV requirements according to EN 60204-1 § 6.4.1, 
we recommend that either the + pole, the – pole or any other part 
of the output circuit shall be connected to the protective earth 
system. This helps to avoid situations in which a load starts 
unexpectedly or can not be switched off when unnoticed earth 
faults occur. 
 
Mar. 2013 / Rev. 1.2  DS--ML60.121-EN 
All parameters are specified at 12V, 4.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
14/23