Техническое Руководство для Puls ML60.121 Power Supply

Скачать
Страница из 23
 
 
ML60.121
 
 
MiniLine-2 
 
12V,
 
4.5A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
14.  E
NVIRONMENT
 
 
Operational temperature 
*)
 
-10°C to +70°C (14°F to 158°F) 
reduce output power according Fig. 14-1
Storage temperature 
-40°C to +85°C  (-40°F to 185°F) 
for storage and transportation 
Output de-rating 
1.4W/°C 
60-70°C   (140°F to 158°F) 
Humidity 
**)
 
5 to 95% r.H. 
IEC 60068-2-30 
Vibration sinusoidal 
2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g 
2 hours / axis 
IEC 60068-2-6 
Shock 
15g 6ms, 10g 11ms 
3 bumps / direction, 18 bumps in total 
IEC 60068-2-27 
Altitude 
0 to 2000m  (0 to 6 560ft) 
without any restrictions 
 
2000 to 6000m  (6 560 to 20 000ft) 
reduce output power or ambient temperature  
see Fig. 14-2 
IEC 62103, EN 50178, overvoltage category II 
Altitude de-rating 
4W/1000m or 5°C/1000m 
> 2000m (6500ft), see Fig. 14-2
Over-voltage category 
III 
IEC 62103, EN 50178, altitudes up to 2000m  
 
II 
altitudes from 2000m to 6000m 
Degree of pollution 
IEC 62103, EN 50178, not conductive 
LABS compatibility 
The unit does not release any silicone or other LABS-critical substances and is suitable for 
use in paint shops. 
*)   Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit. 
**)   Do not energize while condensation is present 
 
 
Fig. 14-1   Output power vs. ambient temp. 
 
Fig. 14-2   Output power vs. altitude 
 
0
-10
0
40
70°C
10
20
30
40
50
60W
60
Ambient Temperature
20
Allowable
Output Power
 
0
0
2000
4000
6000m
10
20
30
40
50
60W
Altitude
A... Tamb < 60°C
B... Tamb < 50°C
C... Tamb < 40°C
A
B
C
Allowable
Output Power
 
 
Mar. 2013 / Rev. 1.2  DS--ML60.121-EN 
All parameters are specified at 12V, 4.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
12/23