Справочник Пользователя для Aclara Power-Line Systems Inc. Y72553-1

Скачать
Страница из 86
60
T W A C S
®
- O R I O N
®
  f o r   U M T   P r o d u c t s   U s e r   G u i d e
Performing Remote Analysis (TWACS NG)
Performing Remote Analysis (TWACS NG)
Complete the following steps to determine if a field visit is required for an 
unresponsive meter. You can end the procedure at any step and correct the problem 
when a cause of failure is determined.
1.   
If communication fails to the transponder, check the path and search state of 
the transponder. You may do this by going to System Monitoring > Edit 
Path > Search States.
2.   
Type in the serial number of the transponder and click 
Lookup
.
If the transponder is currently in the New, Lost or Tentative path state, the 
the TWACS NG will need to search the transponder. The TWACS NG 
Operator will need to be sure that it is in a search state of Ready. The search 
batch job should automatically pick up the transponder for search when the 
next job runs.
3.   
If the transponder is in a Good/Done state, the TWACS NG Operator may 
issue a ping to the transponder. You may do this by going to System 
Monitoring > Test Transponder screen.
4.   
Type in the serial number or Meter/End Device ID and click 
Ping
.
If the ping is successful, communication to the transponder is successful 
and has been verified. If the transponder is still not functioning as expected, 
a field visit will most likely be necessary.
Meter Number
The meter number assigned by 
the utility. IED Serial Number.
[1 – 4294967295]
Serial Number
TWACS Serial Number.
[1 – 4294967295]
Serial Port
Port to which the IED is 
associated.
[1 - 7]
Premises ID Number
Premises ID assigned by utility, 
for the Port of interest (1-7).
String (20)
Port District Number
District Number Assigned by 
Utility.
[0 – 999999]
Port District Location
Location Identifier of the meter 
assigned by the utility.
String(5)
Active Flag
A flag to identify that the device 
is active.
Y, N
Device Type
IED Service Type
0 = Electric
1 = Water
2 = Gas
3 = Propane
4 = Other
0, 1, 2, 3, 4
Field Name
Field Description
Valid Input
DRAFT