C h a p t e r   2 :   A d v a n c e d   P r o g r a m m i n g
4 6
Additional Notes on Contact ID
1. Account numbers must be four digits.
2. If the digit ‘0’ is in the account number substitute the HEX digit ‘A’ for the ‘0’.
3. All reporting codes must be two digits.
4. If the digit ‘0’ is in the reporting code substitute the HEX digit ‘A’ for the ‘0’.
5. To prevent the system from reporting an event program the reporting code for 
the event as [00] or [FF].
Communicator Format Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section [360]
Contact ID Sends Automatic Reporting Codes . . . . . . . . .  Section [381], Option [7]
SIA (Level 2)
SIA is a specialized format that will communicate information quickly using fre-
quency shift keying (FSK) rather than pulses. The SIA format will automatically gen-
erate the type of signal being transmitted, such as Burglary, Fire, Panic etc. The two 
digit reporting code is used to identify the zone or access code number.
If the SIA format is selected the system can be programmed to automatically gener-
ate all zone and access code numbers eliminating the need to program these items.
If the SIA Sends Automatic Reporting Codes option is enabled the system will 
operate as follows:
1. If the reporting code for an event is programmed as [00] the system will not 
attempt to call the central station.
2. If the reporting code for an event is programmed as anything from [01] to [FF] 
the system will AUTOMATICALLY generate the zone or access code number.
3. Bypassed zones will always be identified when partial closing of the system occurs.
The Communicator Call Direction Options can be used to disable reporting of 
events such as Openings/Closings. Also, if all the Opening/Closing reporting codes 
were programmed as [00] the system would not report.
If the SIA Sends Automatic Reporting Codes option is disabled the system will 
operate as follows:
1. If the reporting code for an event is programmed as [00] or [FF] the system will 
not attempt to call central station.
2. If the reporting code for an event is programmed as anything from [01] to [FE] 
the system will send the programmed reporting code.
3. Bypassed zones will not be identified when partial closing of the system occurs.
NOTE:
 The zone number for Zone Low Battery and Zone Fault events will 
not be identified when Programmed SIA is used.
Communicator Format  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section [360]
SIA Sends Automatic Reporting Codes. . . . . . . . . . . . . . .  Section [381], Option [3]
Communicator Call Direction Options . . . . . . . . . . . . . . . . . Sections [361] to [368]
SIA Identifiers  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  Appendix B