C h a p t e r   2 :   A d v a n c e d   P r o g r a m m i n g
4 8
timer expires, the system will transmit the programmed reporting code. If the sys-
tem is disarmed before the timer expires, the alarm will not be transmitted.
The Transmission Delay zone attribute determines which zones will start the timer. 
Transmission Delay Zone Attributes . . . . . . . . . . Sections [101] to [132], Option [7]
Transmission Delay Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section [370]
Low Battery Transmission Delay
When using wireless devices, the battery status of the devices will be monitored by 
the system. If a low battery condition exists, the system will indicate a general 
transmitter low battery trouble. The system will delay reporting the event for the 
number of days programmed as the Low Battery Transmission Delay. This delay 
provides the user with an opportunity to change the batteries on the units before 
the condition is reported to the central station. Instruct the customer on how to 
change the batteries of wireless devices to gain maximum use of this feature. 
NOTE:
 After the first Wireless Device Low Battery reporting code is sent, 
the system will not send additional low battery events until the first low 
battery trouble is restored.
Low Battery Transmission Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section [370]
Cross Zone Police Code Reporting
The system will transmit the Cross Zone Police Code reporting code, if programmed, 
when two different zones are violated within the same armed-to-armed period. 
Cross Zone Police Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section [328]
Delinquency Reporting
The Delinquency feature is used to monitor system activity. When the Delinquency 
Transmission Delay
 timer expires, the system will transmit the Delinquency 
reporting code.
If the system is programmed to monitor Activity Delinquency, the timer will be 
programmed in hours. The timer will start under the following conditions:
• When the system is armed in the Stay mode
• When the system is disarmed
• When a zone is violated and restored while the system is disarmed/Stay armed 
(Interior, Interior Delay, Interior Stay/Away, or Delay Stay/Away zones only).
The activity delinquency timer will be ignored when the system is armed in the Away 
mode. Zones that are bypassed in the [✱][1] Bypass menu will not reset the timer.
If the system is programmed to monitor Closing Delinquency, the timer will be 
programmed in days. The timer will restart every time the system is disarmed. 
Activity/Closing Delinquency . . . . . . . . . . . . . . . . . . . . . .  Section [380], Option [8]
Delinquency Transmission Delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section [370]