Справочник Пользователя для Tait International Limited TBCK4A
TB9400 Installation and Operation Manual
Installation
75
© Tait Limited March 2015
5.1.5
Cabinet and Rack Ventilation
The cooling airflow for the base station enters through the front panel and
exits at the rear of the subrack. For optimum thermal performance, the
heated air that has passed through a base station must not be allowed to re-
enter the air intakes on the front panel. Any space at the front of the cabinet
not occupied by equipment should be covered by a blanking panel. Refer
to
exits at the rear of the subrack. For optimum thermal performance, the
heated air that has passed through a base station must not be allowed to re-
enter the air intakes on the front panel. Any space at the front of the cabinet
not occupied by equipment should be covered by a blanking panel. Refer
to
To allow enough cooling airflow through a cabinet-mounted base station,
we recommend the following:
we recommend the following:
■
an area of at least 23in
2
(150cm
2
) of unrestricted ventilation slots or
holes in front of the air intakes for the fans for each subrack; for
example, thirty 0.25x3.3in (6x85mm) slots will allow the
recommended airflow
example, thirty 0.25x3.3in (6x85mm) slots will allow the
recommended airflow
■
a vent in the top of the cabinet with an area of approximately 23in
2
(150cm
2
) per subrack, or a similar area of ventilation per subrack at the
rear of the cabinet behind each subrack
■
a 2U gap at the top of the cabinet.
Notice The ventilation opening must be unrestricted. If the slots or
holes are covered with a filter, mesh or grille, the open area must be
increased to allow the same airflow as an unrestricted opening.
holes are covered with a filter, mesh or grille, the open area must be
increased to allow the same airflow as an unrestricted opening.
The maximum ambient temperature entering the cabinet must not exceed
+140°F (+60°C).
+140°F (+60°C).
If you are installing multiple subracks in a cabinet, ensure that there will be
enough cooling airflow through the cabinet after the equipment has been
installed. For example, the recommended maximum number of subracks in
a 38U cabinet is five, as shown in
enough cooling airflow through the cabinet after the equipment has been
installed. For example, the recommended maximum number of subracks in
a 38U cabinet is five, as shown in
.
If the base station is installed in a rack or cabinet with other equipment with
different ventilation requirements, we recommend that the base station be
positioned below this equipment.
different ventilation requirements, we recommend that the base station be
positioned below this equipment.
Auxiliary Extractor
Fans
The base station does not require auxiliary extractor fans mounted in the
top of the cabinet. If your cabinet is already fitted with fans, the following
procedures apply:
top of the cabinet. If your cabinet is already fitted with fans, the following
procedures apply:
■
if there are six or more 4.75in (12cm) fans, each capable of extracting
94.2 ft
94.2 ft
3
per minute (160m
3
per hour), they must run continuously
■
if there are fewer than six fans, you must remove them and ensure the
vent in the top of the cabinet has an area of approximately 23in
vent in the top of the cabinet has an area of approximately 23in
2
(150cm
2
) per subrack.
If you have any other configuration, the performance of your system will
depend on how closely you comply with the base station airflow
requirements described above.
depend on how closely you comply with the base station airflow
requirements described above.