SWIFT® Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000NF-E:E 11/9/2017
FWSG FlashScan Wireless System Gateway
LED Indicators
2.5  LED Indicators
The two LEDs on the gateway blink in the same pattern to allow the LED to be viewed from any angle. LED patterns are explained in 
Appendix D.
2.6  Installing the Gateway
2.6.1  Before Installing
Choose a location for the gateway that is clean, dry, and vibration-free. The area should be readily accessible with sufficient room to eas-
ily install and maintain the gateway. Metal obstructions impede the radio frequency communication and should be avoided. Carefully 
unpack the system and inspect for shipping damage if any. All wiring must comply with the national and local codes for fire alarm sys-
tems. 
2.7  Mounting and Wiring
 
2.7.1  Mounting
The gateway has two major pieces, the cover and the mounting plate. The mounting plate is mounted to the wall or ceiling, and field wir-
ing is connected to it. The cover contains the printed circuit board and is fastened to the mounting plate once the wiring is completed. 
Mount the mounting plate directly to an electrical box on the ceiling or wall. The plate mounts directly to a 4˝ square (with and without 
plaster ring), 4˝ octagon, 3 1/2˝octagon, single gang or double gang junction boxes. If an electrical box is not available, the mounting 
plate can be mounted to any flat surface and the wiring can be connected via the knockout points in the mounting plate. 
To mount the gateway:
1.
Pull the wiring through the opening in the mounting plate.
2.
Mount the mounting plate to the junction box or ceiling. See Figure 2.3 below.
3.
Connect field wiring to the terminals, as described in Section 2.7.2.
4.
Connect necessary jumpers where applicable, as described in Section 2.7.3.
5.
To mount the cover, align the locating pins on the cover to the corresponding slots in the mounting plate. See Figure 2.4.
6.
Secure the cover by tightening the mounting screws.
 
!
WARNING: FORMEX SHEET
ENSURE THAT THE FORMEX SHEET INSIDE THE GATEWAY IS NOT REMOVED OR TAMPERED WHILE INSTALLING 
OR CLEANING.
Figure 2.3  Mounting Plate for Wireless Gateway
2.
2
.wm
f
locating pin
locating pin
locating pin