12   OI/266/WIHART-EN | 2600T Series Pressure transmitters
5 Mounting
5 Mounting
5.1 General
Study these installation instructions carefully before proceeding. 
Failure to observe the warnings and instructions may cause a 
malfunction or personal hazard. Before installing the transmitter, 
check whether the device design meets the requirements of the 
measuring point from a measurement technology and safety 
point of view. 
This applies in respect of the:
 — 
Explosion protection certification
 — 
Measuring range
 — 
Gauge pressure stability
 — 
Temperature
  — Operating voltage
The suitability of the materials must be checked as regards 
their resistance to the media. This applies in respect of the:
 — 
Gasket
  — Process connection, isolating diaphragm, etc.
In addition, the relevant directives, regulations, standards, and 
accident prevention regulations must be observed (e.g., VDE/
VDI 3512, DIN 19210, VBG, Elex V, etc.). Measurement 
accuracy is largely dependent on correct installation of the 
pressure transmitter and, if applicable, the associated 
measuring pipe(s). As far as possible, the measuring setup 
should be free from critical ambient conditions such as large 
variations in temperature, vibrations, or shocks.
Important. If unfavorable ambient conditions cannot be avoided for 
reasons relating to building structure, measurement technology, or 
other issues, the measurement quality may be affected. If a remote 
seal with capillary tube is installed on the transmitter, the additional 
operating instructions for remote seals and the related data sheets 
must be observed.
5.2 IP protection & designation
The housings for 266 transmitters are certified as conforming to 
protection type IP66 / IP67 (according to IEC 60529). 
The first number indicates the type of protection the integrated  
electronics have against the entry of foreign bodies, including   
dust. 
“6” means that the housing is dust-proof (i.e., no ingress of    
  dust). The second number indicates the type of protection    
  the integrated electronics have against the entry of water.
The second number indicates the type of protection the hosing 
has against the entry of water. 
“6” means that the housing is protected against water;  
 
  specifically, powerful jets of water under standardized  
 
 conditions. 
“7” means that the housing is protected against water;  
 
  specifically, against the effects of temporary immersion in    
  water under standardized water pressure and temporal  
 
 conditions.
5.3 Mounting the transmitter
5.3.1 Transmitter factory configuration consideration 
The 266 pressure transmitter in your hands has been factory 
calibrated to reflect the published declared performance 
specification; no further calibration is required in normal 
condition. ABB typically configures 266 pressure transmitters 
according to the user requirements. A typical configuration 
includes:
 — 
TAG number
 — 
Calibrated span
 — 
Output linearization
 — 
LCD display configuration
5.3.2 Hazardous area considerations 
The transmitter must be installed in hazardous area only if it is 
properly certified. The certification plate is permanently fixed on 
the neck of the transmitter top housing. The 266 Pressure 
Transmitter Line can have the following certifications: 
ATEX INTRINSIC SAFETY 
  — II 1 G Ex ia IIC T4 and II 1/2 G Ex ia IIC T4
COMBINED ATEX, ATEX FM and FM Canada
  — See detailed classifications
FM Approvals US and FM Approvals Canada: 
  — Intrinsically safe: Class I, II, III, Div. 1, Groups A, B, C, D
  — Class I, Zone 0, AEx ia IIC T6/T4 (FM US)
  — Class I, Zone 0, Ex ia IIC T6/T4 (FM Canada)
IEC (Ex):
  — See detailed classifications
Warning - General risks. Unused port plug must be in accordance 
with the intended type of protection (e.g. intrinsically safe, explosion 
proof, etc.) and degree of protection (e.g. IP6x according to IEC EN 
60529). See also the addendum for “EX SAFETY” ASPECTS AND 
“IP” PROTECTION. In particular, for explosion proof installation, 
remove the red temporary plastic cap and plug the unused opening 
with a plug certified for explosion containment
Warning - General risks. Model 266 enclosure contains aluminium 
and is considered to present a potential risk of ignition by impact or 
friction. Care must be taken into account during installation and use 
to prevent impact or friction.