Справочник Пользователя для ABB WICB

Скачать
Страница из 72
2600T Series Pressure transmitters | OI/266/WIHART-EN   13
5 Mounting
Figure 4: 266 nameplate with PED data
Local keys below label
PRODUCT CODE
SEAL-H
SEAL-L
SPEC.REQUEST
LRL/URL
SPAN LIMITS
POWER SUPPLY
OUTPUT SIGNAL
 ABB S.p.A.
 Made in Italy
 
TS
PS
SERIAL\NUMBER
SENSOR DIAPH.-FILL
FLANGE/CONN.-GASKET/S
H DIAPH.-FILL
L DIAPH.-FILL
SEAL
HW Rev.
MD:
PED:
MWP/OVP
Important. 
In case of a High Static differential pressure transmitter, 
please notice that the Vent/Drain valves can be configured only on 
the process axis (V1).
5.4.2 Devices with PS 200 bar
Devices with a permissible pressure PS ≤200 bar correspond 
to article 3 paragraph (3). They have not been subject to a 
conformity validation. These instruments were designed and 
manufactured acc. to SEP Sound Engineering Practices. 
5.5 Mounting a DP sensor transmitter 
(266DS/266DR) 
The pressure transmitter model 266DS can be mounted directly 
on the manifold. A mounting bracket for wall or pipe mounting 
(2” pipe) is also available as an accessory. For model 266DR 
always mounting brackets should be used. Ideally, the pressure 
transmitter should be mounted in a vertical position to prevent 
subsequent zero shifts.
Important. 
If the transmitter is installed inclined with respect to the 
vertical, the filling liquid exerts hydrostatic pressure on the 
measuring diaphragm, resulting in a zero shift. In such an event, the 
zero point can be corrected via the zero push-button or via the “set 
PV to zero” command. Please refer to the [configuration section] for 
further details. For transmitters without diaphragm seals, please 
read the following considerations on the Vent/Drain.
Attention − Potential damage to transmitter. 
In case of a High 
Static differential pressure transmitter (266DSH.x.H) please always 
open the equalization valve of the manifold (if installed) before 
applying pressure to the transmitter. High Static pressure can 
damage the sensor causing a zero shift and a serious decrease of 
the total performance in terms of accuracy. In this case, please 
perform a full sensor trim.
It is important to mount the transmitter and to lay the process 
Figure 5: Drain/vent valves configuration (respectively V1, V2, V3)
5.4 Pressure Equipment Directive (PED) (97/23/CE)
5.4.1 Devices with PS >200
Devices with a permissible pressure PS >200 bar have been 
subject to a conformity validation. The data label includes the 
following specifications:
piping so that gas bubbles, when measuring liquids, or 
condensate when measuring gases, will flow back to the 
process and not enter the transmitter measuring chamber. 
Optional Vent/drain valves (code V1/V2/V3) on the transmitter 
are located on the sensor flanges. 
The transmitter has to be positioned so that these drain/vent 
valves will be located higher than the taps on liquid service in 
order to allow the venting of entrapped gas or below the taps 
on gas service in order to allow the air to vent off or 
condensate to drain off. For safety reasons, take care of the 
drain/vent valves position so that when the process fluid is 
removed during the drain/vent operation it is directed down 
and away from technicians. It is recommended to mount the 
transmitter to prevent this possible source of damage for 
unskilled operators.