Circuit Diagram 
 
 
 
 
 
 
 
 
 
 
 
 
Note:  
•  Conductor of at least 0.75mm
2
 shall be used 
for wiring of defrost and evaporator fan 
control load. 
•  Conductor of at least 1.0mm
2
 shall be used 
for wiring of compressor control load. 
•  The inrush current for compressor may be 
20A instead of 8A during the 1 second 
period at the start. 
 
Notes for Installation  
•  Before wiring, please read the 
instructions carefully and be sure to 
understand the function of every 
contact so that you can make correct 
wire connections. Control loads cannot 
exceed the ratings. 
•  The temperature controller cannot be 
installed in an area where water flows, 
a dirty area, an area of high moisture, 
or in an area with high temperatures. 
Please pay attention to EMC problems 
and prevent the  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
temperature controller from collisions 
with other objects. 
•  The sensor cable leads must be kept 
away from the main supply in order to 
avoid high frequency noise. 0.75‐
1.5mm
2
 flexible cords should be used 
for wiring control load terminals. 
•  The evaporator sensor must be installed 
between the fins of the evaporator in 
the area where ice is the thickest. Do 
not place the evaporator sensor near 
the electric heater. 
•  If the temperature controller is 
disturbed, please cut off the power 
supply and reset. The software of this 
product belongs to grade A, and it does 
not apply to safe control. 
•  Please don’t dismantle the controller. If 
you need repairing or you have any 
problems in using the controller, please 
do not hesitate to contact our 
company.