– 13 –
SMMS-i
Installation Manual
SMMS-i
Installation Manual
(5)
Branching section
È
Indoor unit
Indoor unit 
connecting pipe
Connecting pipe size of indoor unit
(6)
Branching section Y-shaped 
branching joint
Selection of branching section (Y-shaped branching joint)
(7)
Branching section Branching header
Selection of branching section (Branching header)
*2: Up to a total of 6.0 maximum equivalent to HP capacity codes is connectable to one line 
after branching of header. When the total capacity codes of all outdoor units are 12 to below 
26 (equivalent to HP) and you use a branching header for the first branching section, use 
a RBM-HY2043E or RBM-HY2083E regardless of the total capacity codes of outdoor units 
at downstream side. In addition, you cannot use a branching header for the first branching 
section when the total capacity codes of all outdoor units are over 26 (equivalent to HP).
(8)
Branching section
Outdoor unit 
connection piping 
kit (For linking of 
outdoor units)
Outdoor unit connection piping kit (For linking of outdoor units) 
*3: Downstream side when regarding the main piping as the start point 
No.
Piping parts
Name
Selection of pipe size
Remarks
Capacity rank
Gas side
Liquid 
side
007 to 012 type 
15m or less real length
Ø9.5
Ø6.4
Real length exceeds 15m
Ø12.7
Ø6.4
015 to 018 type
Ø12.7
Ø6.4
024 to 056 type
Ø15.9
Ø9.5
072 to 096 type
Ø22.2
Ø12.7
Total capacity code of indoor units
Model name
Equivalent to HP
Equivalent to 
capacity
Y-shape 
branching joint
Below 6.4
Below 18.0
RBM-BY55E
6.4 to below 14.2
18.0 to below 40.0
RBM-BY105E
14.2 to below 25.2
40.0 to below 70.5
RBM-BY205E
25.2 or more
70.5 or more
RBM-BY305E
Total capacity code of indoor units
Model name
Equivalent to HP
Equivalent to 
capacity
*2
Branching header
For 4 
branches
Below 14.2
Below 40.0
RBM-HY1043E
14.2 to below 25.2 40.0 to below 70.5 RBM-HY2043E
For 8 
branches
Below 14.2
Below 40.0
RBM-HY1083E
14.2 to below 25.2 40.0 to below 70.5 RBM-HY2083E
Total capacity code of outdoor units
*3
Model name
Equivalent to HP
Equivalent to 
capacity
Outdoor unit 
connection piping 
kit (For linking of 
outdoor units)
Below 26.0
Below 73.0
RBM-BT14E
26.0 or more
Above 73.0
RBM-BT24E
„
Allowable length of refrigerant pipes and allowable height 
difference between units 
D
Follower unit
Height 
difference 
between 
outdoor 
units 
H3 
≤ 5 m
Height 
difference 
between 
indoor units:
H2 
≤ 40 m
Outdoor unit
Ld
Lc
Lb
La
LB
LA
Outdoor unit connection piping kit 
(For linking of outdoor units)
Ou
tdoo
r un
it c
o
nnec
ting
 p
ipes
 
The longest piping between outdoor units: 
L0 
≤ 25 m
Ma
in
 pi
pi
ng
 L
1
Height 
difference 
between 
outdoor 
and indoor 
units: 
H1 
≤ 70 m
First branching
section
L3
Y-shaped 
branching joint 
L4
L5
L6
Indoor unit
f
g
h
i
j
The longest piping length from the first branch: Li 
≤ 90 m
The longest piping length: L 
≤ 235 m
Indoor unit
a
b
c
d
e
(j)
Indoor unit connecting 
pipe
Branching header 
Y-shaped branching 
joint 
L7
A
Header 
unit
B
Follower 
unit
C
Follower 
unit
25-EN
26-EN
+00EH99871699_01EN.book  Page 13  Thursday, August 26, 2010  4:41 PM