– 14 –
SMMS-i
Installation Manual
EN
SMMS-i
Installation Manual
System restriction
Cautions for installation
• Set the outdoor unit first connected to the bridging pipe to the indoor units as the header unit.
• Install the outdoor units in order of their capacity codes: A (header unit) 
≥ B ≥ C ≥ D
• When connecting gas pipes to indoor units, use Y-shaped branching joints to keep pipes level.
• When piping to outdoor units using Outdoor unit connection piping kits, intersect the pipes to the outdoor unit 
and those to indoor units at a right angle as shown in figure 1 on “6. INSTALLATION OF THE OUTDOOR UNIT”
Do not connect them as in figure 2 on “6. INSTALLATION OF THE OUTDOOR UNIT”.
Allowable length and allowable height difference of refrigerant piping
*1: Farthest outdoor unit from the first branch: (D), farthest indoor unit: (j)
*2: If the total capacity of outdoor units is 46HP or more, make the equivalent length 70m (real length 50m) or less. 
*3: Make the difference 65m or less if the height difference between outdoor and indoor units (H1) is more than 3m.
*4: Make the difference 50m or less if the height difference between indoor units (H2) is more than 3m. 
*5: Make the difference 30m or less if the height difference between indoor units (H2) is more than 3m.
Outdoor unit combination
Up to 4 units
Total capacity of outdoor units 
Up to 48 HP
Indoor unit connection 
Up to 48 units
Total capacity of indoor units
(varies depending on the height difference between 
indoor units.)
H2 
≤ 15m
135% of outdoor units’ capacity
15m < H2
105% of outdoor units’ capacity
Item
Allowable 
value
Pipes
Pipe length
Total extension of 
pipe (liquid pipe, 
real length)
Less than 96kW
Less than 34HP or 
less
300m
LA + LB + La + Lb + Lc + Ld + L1 + L2 + L3 + L4 
+ L5 + L6 + L7 + a + b + c + d + e + f + g + h + i + j
96kW or more
34HP or more
500m
Farthest piping length L (*1)
Equivalent length
235m
LA + LB + Ld + L1 + L3 + L4 + L5 + L6 + j
Real length
190m
Main piping length
Equivalent length
120m (*2)
L1
Real length
100m (*2)
Farthest equivalent piping length from the first branch Li 
(*1)
90m (*3)
L3 + L4 + L5 + L6 + j
Farthest equivalent piping length between outdoor units L0 
(*1)
25m
LA + LB + Ld (LA + Lb, LA + LB + Lc)
Maximum equivalent piping length of pipes connected to 
outdoor units
10m
 La, Lb, Lc, Ld
Maximum real length of pipes connected to indoor units
30m
a, b, c, d, e, f, g, h, i, j
Maximum equivalent length between branching sections
50m
L2, L3, L4, L5, L6, L7
Height 
difference
Height between outdoor and indoor 
units H1
Upper outdoor 
units
70m (*4)
Lower outdoor 
units
40m (*5)
Height between indoor units H2
40m
Height between indoor units H3
5m
„
Airtightness test
After the refrigerant piping has been finished, execute an airtight test.
For an airtight test, connect a nitrogen gas canister as shown in the figure on the next page and apply pressure.
• Be sure to apply pressure from the service ports of the packed valves (or ball valves) at the liquid side, gas side 
and balance pipe side.
• An airtight test can only be performed at the service ports at the liquid side, gas side and balance pipe side on 
header unit.
• Close the valves fully at the gas side, liquid side and balance pipe side. As there is a possibility that the nitrogen 
gas will enter into the cycle of outdoor units, re-tighten the valve rods at the liquid side and balance pipe side 
before applying pressure.
(When using MAP140 or MAP160, you do not have to re-tighten the liquid side valve rod as their valves at the 
liquid side are ball valves.)
• For each refrigerant line, apply pressure gradually in steps at the liquid side, gas side and balance pipe side.
Be sure to apply pressure at the gas side, liquid side, and balance pipe side.
WARNING
Never use oxygen, flammable gases, or noxious gases in an airtight test.
Able to detect a serious leakage
1. Apply pressure 0.3MPa (3.0kg/cm²G) for 5 minutes or more.
2. Apply pressure 1.5MPa (15kg/cm²G) for 5 minutes or more.
Available to detect slow leakage
3. Apply pressure 3.73MPa (38kg/cm²G) for approx. 24 hours.
• If there is no pressure decrease after 24 hours, the test is passed.
V
L
V
H
Connected to indoor unit
Main piping
Gas side valve fully closed
Low pressure
gauge
High pressure
gauge
Brazed
Header outdoor unit
Fully 
closed
Fully 
closed
Connected to other follower units
Balanced pipe side valve 
fully closed
Liquid valve fully closed
Service port
Service port
Copper pipe
Copper 
pipe
Nitrogen 
gas
Reducing 
valve
Gauge 
manifold
To gauge manifold
Liquid-side service port
Gas-side valve
Balance
service port
Balance valve
Piping at site
Piping at site
Piping at site
To outdoor unit
To 
outdoor 
unit
Liquid-side valve
Packed valve details
To 
outdoor 
unit
Gas-side 
service port
Service port
27-EN