5.3.7  Trip-out time (RCDt)
Trip-out time measurement is used to verify the effectiveness of the RCD. This is achieved by a 
test simulating an appropriate fault condition. Trip-out times vary between standards and are listed 
below.
Trip-out times according to EN 61008 / EN 61009:
½
×I
∆N
*)
I
∆N
2
×I
∆N
5
×I
∆N
General (non-
delayed) RCDs
t
∆ 
< 300 ms
t
∆ 
< 300 ms
t
 < 150 ms
t
 < 40 ms
Selective (time-
delayed) RCDs
t
∆ 
< 500 ms
130 ms < t
∆ 
500 ms
60 ms < t
 < 
200 ms
50 ms < t
 < 
150 ms
Trip-out times according to IEC 60364-4-41:
½
×I
∆N
*)
I
∆N
2
×I
∆N
5
×I
∆N
General (non-
delayed) RCDs
t
∆ 
< 999 ms
t
∆ 
< 999 ms
t
 < 150 ms
t
 < 40 ms
Selective (time-
delayed) RCDs
t
∆ 
< 999 ms
130 ms < t
∆ 
999 ms
60 ms < t
 < 
200 ms
50 ms < t
 < 
150 ms
Trip-out times according to BS 7671:
½
×I
∆N
*)
I
∆N
2
×I
∆N
5
×I
∆N
General (non-
delayed) RCDs
t
∆ 
< 1999 ms
t
∆ 
< 300 ms
t
 < 150 ms
t
 < 40 ms
Selective (time-
delayed) RCDs
t
∆ 
< 1999 ms
130 ms < t
∆ 
< 500 
ms
60 ms < t
 < 
200 ms
50 ms < t
 < 
150 ms
*) Test current of ½
×I
∆N
 cannot cause trip-out of the RCDs. 
How to perform trip-out time measurement:
Step 1
 
 Select FI/ RCD TEST (RCD) with the function selector switch. Use the 
/
. keys to se-
lect RCDt (trip-out time of the RCD). The following menu is displayed:
Fig. 5.17: Trip-out time measurement menu
 
 
Connect the test cable to the BENNING IT 110/ BENNING IT 120 B.
Step 2 
Set the following measuring parameters:
 
 
 Nominal differential trip-out current
 
 
 Nominal differential trip-out current multiplier
 
 
 RCD type, and
 
 
 Test current starting polarity