Step 2 
By using cursor keys the following parameters can be set in this measurement:
 
 
  Nominal residual current
 
 
 RCD type
 
 
 Test current starting polarity
Step 3
 Follow the connection diagram shown in figure 5.15 (see the chapter Contact voltage
to perform trip-out current measurement. Use the Help function if necessary. 
Step 4 
Check the displayed warnings and online voltage/terminal monitor before starting the 
measurement. If OK, press the TEST key. After performing, the measurement results 
with PASS/FAIL indication appear on the display. 
Fig. 5.20: Example of trip-out current measurement result
Displayed results:
I
∆:
 
Trip-out current
U
Ci:
 
Contact voltage
tI:   
Trip-out time
Save displayed results for documentation purposes. Refer to chapter 6.1 for further information on 
setting functions and saving of measurement results (BENNING IT 120 B only).
Note:
-   Parameters set in this function are also kept for other RCD functions.
-   RCD trip-out time measurement will be performed only if contact voltage at nominal differential 
current is lower than the set limit contact voltage.
-   The measurement of contact voltage in pre-test does not normally trip an RCD. However, the 
trip limit may be exceeded as a result of leakage current flowing to the PE protective conductor
or via a capacitive connection between L and PE conductors.
5.3.9  AUTO test
The purpose of the autotest function is to perform complete RCD testing and measurement of 
the relevant parameters (contact voltage, loop impedance (fault loop resistance) and trip-out 
time at different fault currents) in one set of automatic tests, controlled by the BENNING IT 110/ 
BENNING IT 120 B. If any false parameter is noticed during autotest, the individual parameter test 
has to be used for further investigation.
How to perform RCD autotest:
Step 1
 
Select FI/ RCD TEST (RCD) with the function selector switch. Use the 
/
 keys to se-
lect RCD autotest function. The following menu is displayed: 
Fig. 5.21: RCD autotest menu