Справочник Пользователя для Beha Amprobe GT-800 PRO KITVDE-tester 4472081
Модели
4472081
GT-600/GT-800 Instruction Manual
19
Display explanation:
Figure 8: Display in protective bonding test R
PE
1 ...... “
F:
AUT” / “
F:
MAN” soft menu key, for selection of automatic /
manual start and store function.
2 ....... “COMP” soft menu key, for test lead compensation.
3 ...... “Im” soft menu key, for test current selection (0.2 A or 5 A).
4 ...... “LIM” soft menu key, for pass/fail limit value setting.
5 ...... Test result status ( ... result OK, X ... result not OK).
6 ...... Selected test current (0.2 A or 5 A).
7 ...... Pre-set pass/fail limit value.
8 ...... Test lead compensation mark (C ... compensated, blank .. not
3 ...... “Im” soft menu key, for test current selection (0.2 A or 5 A).
4 ...... “LIM” soft menu key, for pass/fail limit value setting.
5 ...... Test result status ( ... result OK, X ... result not OK).
6 ...... Selected test current (0.2 A or 5 A).
7 ...... Pre-set pass/fail limit value.
8 ...... Test lead compensation mark (C ... compensated, blank .. not
compensated).
9 ...... Selected mode of start and save function (MAN, AUT).
MAN (Manual) ... Use START key to start the measurement.
AUT (Automatic) ... The test is started automatically after connecting
PROBE 1 to conductive part of tested appliance. Result is
automatically stored to last selected storage address. START key is not
active in this mode.
10 .... Function selected by the rotary switch (6).
11 .... Test result and unit.
Note:
In case that protective bonding test fails, the pass/fail limit value can be
recalculated by using the “LIM” and “CALC” keys and entering the length
and cross section of the mains lead. The last measurement value will be
deleted, and a new test has to be performed.
11 .... Test result and unit.
Note:
In case that protective bonding test fails, the pass/fail limit value can be
recalculated by using the “LIM” and “CALC” keys and entering the length
and cross section of the mains lead. The last measurement value will be
deleted, and a new test has to be performed.