20
Pass/fail limit value calculation:
Cross section A
Cable length L
Limit value
1.5 mm
2
5 m
0.3
5 ... 12.5 m
0.4
12.5 ... 20 m
0.5
20 ... 27.5 m
0.6
27.5 ... 35 m
0.7
35 ... 42.5 m
0.8
42.5 ... 50 m
0.9
50 m
1.0
2.5 ... 50 mm
2
1 ... 50 m (res. 0.5 m)
R
LIM
=
.L/A
Where:
... 0.01786 mm
2
/m (specific resistance of Cu)
L .. cable length in m
A .. cross section in mm
A .. cross section in mm
2
Specific information that can be shown on the display:
Information displayed
Description
TEST LEAD
NOT COMPENSATED
Test lead is not compensated (no “C” mark on
the display)! It is recommended to
compensate the test lead.
the display)! It is recommended to
compensate the test lead.
>5
, NOT COMPENSATED
Compensation was not successfully done due
to too high compensation value (>5.00
to too high compensation value (>5.00
)!
COMP?
Test lead is wrong compensated (negative R
PE
result
0.05 ). Compensate the test lead
again.
EXTERNAL VOLTAGE
External voltage is applied to one or more
test terminals, see the explanation in section
“Pre-Tests and Protection, Functions and
Messages”.
test terminals, see the explanation in section
“Pre-Tests and Protection, Functions and
Messages”.
USE PROBE 1
Test lead is connected to PROBE 2. Reconnect
it to PROBE 1.
it to PROBE 1.
>11.00
X
R
PE
value higher than 11.00
(over-range),
possibly because of open test lead.
In order to save displayed measurement result, press the “SAVE” function
key (F5) twice, for further instructions see the “Memorizing example”
section.
section.